Figure 3-24 Function Block Diagram Of Figure 3-23 - Honeywell VPR100 User Manual

Table of Contents

Advertisement

Programming and Operating Concepts
In Figure 3-24, the analog input function block AI1 is depicted processing the resistance values produced
by the RTD. The resulting water temperature measurements (AI1 OV) are then fed to the process variable
input (PV) of the LP1 control loop block. Note how LP1 has been defined as a split output control loop
using the notation "TYPE = SPLIT." Unique to this control loop is the defined range of its output value,
LP1 OV. Where the standard control loops mentioned thus far have had outputs ranging exclusively
between 0 and 100%, the % values of the split output control loop vary between -100 and 100. 0% is
considered the midpoint for this control loop's output range. When brought on-line, a 0 to 100% output
value will be generated by LP1 when hot water is needed to maintain the temperature at set point. When the
addition of cold water is necessary, the loop's output will assume a value between 0 and -100%. Note that
to externalize the control signals generated by LP1, two analog output blocks, AO1 and AO2, will be used.
AO1's 4 to 20 mA signal will be tied to the hot water valve actuator, while the actuator that adjusts the
position of the cold water valve will receive its mA control signal from AO2. To provide AO1 and AO2
with usable input driving signals, LP1's output will be applied to a function called a "standard splitter (STD
SPLITTER)." Made from one of the instrument's calculated value function blocks ("CV's"), the standard
splitter will essentially be a mechanism that translates the % values of the split output control loop into two
distinct 0 to 100% signals. They will be applied to the inputs of AO1 and AO2 and, as such, will drive and
linearly correspond with AO1 and AO2's 4 to 20 mA outputs.
100 Ω
PLATINUM
RTD
The two outputs on CV1 that will drive AO1 and AO2 are respectively labeled "CV1 A1" and "CV1 A2."
CV1's basic operation is described by a plot of these outputs versus LP1 OV. Shown in the lower left of
Figure 3-24, the plot demonstrates that CV1 will produce a 0 to 100% value at its CV1 A1 output when LP1
calls for an output level between 0 and 100 %. CV1 A2 will remain at 0%. When applied to AO1, the CV1
A1 value will activate the 4 to 20 mA signal needed at the hot water valve actuator to make the water
temperature in the vessel rise. Similarly, when LP1 calls for an output level between 0 and -100%, CV1
will produce a corresponding 0 to 100 % value at CV1 A2. This time, CV1 A1 will remain at 0% and the
CV1 A2 value generated will induce the introduction of cold water into the vessel to cool its contents down.
Note the function block diagram's use of three back calculated feedback paths. Two such paths are labeled
AO1 BC and AO2 BC. They are connected to CV1 from the analog output function blocks at inputs
denoted "FB1" and "FB2." CV1 BC, the third feedback path, runs from CV1 to the FB input of LP1. All
three feedback paths work together to acknowledge to LP1 that the appropriate output signals have been
generated in response to the % output levels the loop has called for.
66
AI1 OV
AI1
PV
INPUT TYPE = PT100
TYPE = SPLIT
100%
CV1 A2
0
-100%
0
100%
LP1 OV

Figure 3-24 Function Block Diagram Of Figure 3-23

VPR & VRX – User Manual
CV1 BC
FB1
A1
FB
LP1 OV
LP1
IN
CV1
TYPE = STD SPLITTER
A2
FB2
100%
CV1 A1
0
AO1 BC
4 TO 20 mA
CV1 A1
IN
AO1
4 TO 20 mA
IN
AO2
CV1 A2
AO2 BC
12/00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrx100Vrx150

Table of Contents