750-484 2 AI 4-20 mA HART Ex i
"PROFIBUS-DP >Other FIELD DEVICES >I/O >WAGO I/O-SYSTEM
750".
8.
Change the address to the station address of the WAGO PROFIBUS DP/V1
coupler/controller previously set on the DIP switch.
9.
Now expand the device catalog and using "Drag&Drop" add the remaining
I/O modules that you have plugged into your fieldbus node on the
coupler/controller.
In doing so, you will find a total of five entries for the HART I/O Module
corresponding to the operating modes.
You will find a description of the different entries with a list of all the
associated parameters in the section "Operating Modes" > ... > "Setting Up
via GSD".

Figure 26: HW Config in STEP7

10.
Select the entry corresponding to the required operating mode and
incorporate this into your configuration.
11.
Double-clicking on a module in the configuration tree structure will open a
module-specific parameterizing dialog in which you can set the parameters
for the PROFIBUS Coupler 750-333 or Controller 750-833, the HART I/O
module and other parameterizable I/O modules.
Set the required parameter data.
12.
Next save and translate the network configuration and transfer the new
project to the PLC.
10.3
FDT/DTM with the PROFIBUS DP/V1 750-333,
750-833
In the operating mode "2AI + acyclic PROFIBUS services", when the HART I/O
module is connected to a PROFIBUS Coupler 750-333 or Controller 750-833, it is
also possible to carry out HART communication by means of the FDT/DTM
frame application "WAGOframe". The device driver
"Profibus/HARTGatewayDTM 759-360" is available for using the FDT/DTM
Manual
V 1.2.0 HW-Version 04, SW-Version 03
Description of Operation
67