WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
4.2.3
Ni1000 TK5000
The 750-461/000-009 version calculates the resistance values of Ni1000-TK5000
sensors and outputs the data as temperature values. The temperature values are
displayed at a resolution of 1 digit per 0.1 °C in one word (16-bit). Temperature
values below 0 °C are represented in two's complement binary. As a result, 0 °C
corresponds to the numeric value 0x0000 and 100 °C to the numeric value
0x03E8 (dec. 1000). The possible numeric range corresponds to the defined
temperature range of -30 °C to +122 °C for type Ni1000 TK5000 sensors.
Table 23: Process Image, Ni1000 TK5000, with Wire Break Diagnostics
Temperature
°C
< −30.0
−30.0
−10.0
10.0
30.0
50.0
70.0
90.0
122.0
> 122.0
Wire break at RL
1)
Process values below 0 °C are represented in two's complement binary.
The measured value can exceed a decimal range of -300 to +1220 before
limitation takes effect.
Manual
Version 1.4.0
Resistance
Ω
Binary
< 60
'0010.0001.0011.0100'
< 871
'1000.0000.0000.0001'
871
'1111.1110.1101.0100'
956
'1111.1111.1001.1100'
1044
'0000.0000.0110.0100'
1137
'0000.0001.0010.1100'
1235
'0000.0001.1111.0100'
1337
'0000.0010.1011.1100'
1444
'0000.0011.1000.0100'
2891
'0000.0100.1100.0100'
> 1627
'0010.0001.0011.0100'
0010.0001.0011.0100'
1)
Numeric value
Hex.
0x2134
0x8001
−32767
0xFED4
0xFF9C
0x0064
0x012C
0x01F4
0x02BC
0x0384
0x04C4
0x2134
0x2134
Process Image
31
Status
LED
Byte
Error
Hex.
AI 1, 2
Dec.
8500
0x42
ON
0x41
ON
−300
0x00
OFF
−100
0x00
OFF
100
0x00
OFF
300
0x00
OFF
500
0x00
OFF
700
0x00
OFF
900
0x00
OFF
1220
0x00
OFF
8500
0x42
ON
8500
0x42
ON