22
Device Description
3.6.5

Climatic Environmental Conditions

Table 13: Technical Data – Climatic Environmental Conditions
Operating temperature range
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
Storage temperature range
Storage temperature range for
components with extended
temperature range (750-xxx/025-xxx)
Relative humidity
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
3.6.6

Connection Type

Table 14: Technical Data – Field Wiring
Wire connection
Cross section
Stripped lengths
Table 15: Technical Data – Data Contacts
Data contacts
WAGO-I/O-SYSTEM 750
750-461 2AI Pt100/RTD
0 °C ... 55 °C
−20 °C ... +60 °C
−25 °C ... +85 °C
−40 °C ... +85 °C
Max. 5 % ... 95 % without condensation
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
®
CAGE CLAMP
0.08 mm² ... 2.5 mm², AWG 28 ... 14
8 mm ... 9 mm / 0.33 in
Slide contact, hard gold plated, self-
cleaning