4. Output specifications (Relay output type)
Item
Output Points
Connection type
Output type
External power supply
Output circuit insulation
Indication of output operation
Resistance load
Max. load
Inductive load
Open circuit leakage current
Min. load
OFF ON
Response time
ON OFF
Output circuit configuration

16.3.2 Parts identification and terminal arrangement

Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower
four points.
With cover
240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
Supplying power to the relay coil will light the LED indicator lamp on panel.
The total resistance load current per common should be as follows:
4 output points/common: 8A or less
Without cover
Input indicator
lamps (LED lamps)
Output indicator
lamps (LED lamps)
16 Input/Output Extension Blocks
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
FX
-8ER
2N
4 points
Vertical terminal block (M3 screws)
Relay
30V DC or less
Mechanical insulation
2A/point
80VA
→ For the product life, refer to Subsection 14.4.3.
→ For cautions on external wiring, refer to Subsection 12.1.3.
-
5V DC, 2mA (reference values)
Approx. 10ms
Approx. 10ms
Load
Y
DC power
supply unit
COM1
Fuse
Rear line
extension
connector
11
12
13
14
15
16
17
18
19
20
255