Fx-16Eyt-Tb, Fx-16Eyt-H-Tb; Specifications - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
20.8

FX-16EYT-TB, FX-16EYT-H-TB

The FX-16EYT(-H)-TB is used by connecting it to the FX
Connectable models
The applications shown below are not supported.
Pulse outputs
Time division inputs
Time division output Seven segment with latch (SEGL) instruction

20.8.1 Specifications

Item
Input/output
circuitry
Load voltage
Resistance
load
Max.
load
Inductive
load
Open-circuit
leakage current
Res-
*1
OFF ON
ponse
*1
OFF ON
time
Output
element's
ON voltage
Circuit isolation
Operation
indicators
Power
consumption
*1.
This response time does not include the response delay at the PLC.
Output Connector
FX
-16EYT-C (sink output)
2N
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width modulation
(PWM) instruction, DOG search zero return (DSZR) instruction, batch data positioning mode (TBL) instruction,
absolute current value read (ABS) instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV)
instruction, drive to increment (DRVI) instruction, drive to absolute (DRVA) instruction
Input matrix (MTR) instruction, digital switch (DSW) instruction
FX-16EYT-TB
Photo-
3.3k
coupler
24+
LED
CN1
24V DC
Connector
7mA
side
0.5A/point
The total load current of resistance loads per common
terminal should be the following value.
4 output points/common terminal: 0.8A or less
12W/24V DC
The total of inductive loads per common terminal should
be the following value.
4 output point/common terminal: 19.2W or less/24V
DC
0.2ms or less/24V DC
1.5ms or less/24V DC
Activation of the photo-coupler will light the LED indicator lamp on panel.
20.8 FX-16EYT-TB, FX-16EYT-H-TB
series output extension block (transistor).
2N
Unsupported Applications
Transistor output
Fuse
0 to 7
3.3k
24+
LED
5-30 V
CN1
DC
Connector
COMn
side
External
wiring
5-30 V DC
The total load current of resistance loads per common
terminal should be the following value.
4 output points/common terminal: 3A or less
The total of inductive loads per common terminal should
be the following value.
4 output point/common terminal: 72W or less/24V
DC
0.1mA / 30V DC
1.5V
Photo-coupler isolation
2.7W (112mA 24V DC)
20 Terminal Block
FX-16EYT-H-TB
Fuse
Photo-
0 to 7
coupler
5-30 V
DC
24V DC
7mA
COMn
External
wiring
1A/point
24W/24V DC
0.3ms or less/24V DC
4ms or less/24V DC
373