External Dimensions - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
3. Output specifications (transistor output type)
Item
Output Points
Connection type
Output unit/type
External power supply
Output circuit insulation
Indication of output operation
Resistance load
Max. load
Inductive load
Open circuit leakage current
Min. load
OFF ON
Response time
ON OFF
Output circuit configuration

15.4.2 External dimensions

FX
-32ET-ESS/UL
2N
2- 4.5 mounting holes
140 (5.52") (mounting hole pitch)
150 (5.91")
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL, FX2N-48ET-DSS
FX
-32ET-ESS/UL
2N
16 points
Removable terminal block (M3 screw)
Activation of the photo-coupler will light the LED indicator lamp on panel.
0.5A/point
The total load current per common terminal
should be the following value.
4 output points/common terminal: 0.8A or
less
12W/24V DC
The total of inductive loads per common
terminal should be the following value.
4 output point/common terminal: 19.2W or
less/24V DC
0.2ms or less/200mA (at 24V DC)
0.2ms or less/200mA (at 24V DC)
Load
DC power
supply
Fuse
A common number applies to the of [+V ].
Unit : mm (inches)
87 (3.43")
15 Input/Output Powered Extension Units
FX
-48ET-ESS/UL, FX
2N
24 points
Transistor/source output
5-30 V DC
Photo-coupler insulation
0.5A/point
The total load current per common terminal
should be the following value.
4 output points/common terminal: 0.8A or
less
8 output points/common terminal: 1.6A or
less
12W/24V DC
The total of inductive loads per common
terminal should be the following value.
4 output point/common terminal: 19.2W or
less/24V DC
8 output points/common terminal: 38.4W or
less/24V DC
0.1mA/30V DC
-
Y
+V
9 (0.36")
11
-48ET-DSS
2N
12
13
14
15
16
17
18
19
20