External Wiring For Relay Output Type; Product Life Of Relay Contacts; Handling Of Relay Output - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
12.1

External Wiring for Relay Output Type

This section explains relay outputs and external wiring.
For the relay output specifications, refer to the following.
→ For the specifications on the input/output powered extension unit, refer to Chapter 15.

12.1.1 Product life of relay contacts

12.1.2 Handling of relay output

1. Output terminal
One common terminal is used for 4 or 8 relay output points.
The common terminal blocks can drive loads of different circuit
voltage systems (for example,100V AC and 24V DC).
2. External power supply
Use an external power supply of 30V DC or less or 240V AC or less (250V AC or less when the unit does not
comply with CE, UL or cUL standards) for loads.
3. Circuit insulation
The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and
contact. The common terminal blocks are separated from one another.
4. Display of operation
When power is applied to the output relay coil, the LED is lit, and the output contact is turned on.
5. Response time
The response time of the output relay from when the power is applied to the coil until the output contact is
turned on and from when the coil is shut off until the output contact is turned off is approx. 10ms.
6. Output current
At a circuit voltage of 240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL
standards), a resistance load of 2A per point or an inductive load of 80VA or less (100V AC or 200V AC) can
be driven.
→ For the life of the contact for switching an inductive load, refer to Subsection 14.4.3.
When an inductive load is switched, connect a diode (for commutation) or a surge absorber in parallel with
this load.
DC circuit
Diode (for commutation)
AC circuit
Surge absorber
7. Open circuit leakage current
Because there is no leakage current even while output contacts are OFF, the neon ball, etc. can be driven
directly.
→ For the specifications on the main unit, refer to Subsection 4.4.1.
→ For the specifications on the input/output extension block, refer to Chapter 16.
→ For product life of relay contacts, refer to Subsection 14.4.3.
12 Output Wiring Procedures
12.1 External Wiring for Relay Output Type
Load
Y
0
Y
1
Fuse
24V DC
COM1
Load
Y
4
Y
5
Fuse
100V AC
COM2
11
12
13
14
15
PLC
16
17
18
19
20
175