14.6.4 Error Code List and Action

When a program error occurs in the PLC, the error code is stored in special data registers D8060 to D8067,
D8438 and D8449. Take action based on the following information.
PLC
Error
operation
code
at error
occurrence
I/O configuration error [M8060(D8060)]
The head number of unconnected I/O devic
Example: When X020 is unconnected
Ex-
Continues
ample:
operation
1020
1st to 3rd digits: Device number
4th digit: I/O type
(1 = input (X), 0 = output (Y))
Example: When 1020 is stored in D8060
Inputs X020 and later are unconnected.
Serial communication error 2 [M8438(D8438)]
0000
No error
3801
Parity, overrun or framing error
3802
Communication character error
3803
Communication data sum check error
3804
Communication data format error
3805
Command error
3806
Communication time-out detected
3807
Modem initialization error
Continues
3808
N:N network parameter error
operation
3809
N:N Network setting error
3812
Parallel link character error
3813
Parallel link sum error
3814
Parallel link format error
3820
Inverter communication error
3821
MODBUS communication error
3840
Special adapter connection error
PLC hardware error [M8061(D8061)]
0000
No error
6101
Memory access error
6102
Operation circuit error
Stops
operation
6103
I/O bus error (M8069 = ON)
6104
Powered extension unit 24 V failure (M8069 = ON)
6105
Watchdog timer error
6106
I/O table creation error (CPU error)
216
Contents of error
1 0 2 0
BCD conversion value
Device number: 10 to 177
1: Input (X), 0: Output (Y)
14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
Unconnected I/O relay numbers are programmed.
The PLC continues its operation. Modify the program, check
wiring connection, or add the appropriate unit/block.
Ethernet
communication,
computer link and programming:
Ensure the parameters are correctly set according to their
applications.
N:N network, parallel link, MODBUS communication, etc.:
Check programs according to the applications.
Remote maintenance:
Ensure modem power is ON and check the settings of the
AT commands.
Wiring:
Check the communication cables for correct wiring.
Check connection of the special adapter.
When the memory cassette is used, check whether it is
mounted correctly.
If the problem persists or if the memory cassette is not used,
something may be malfunctioning inside the PLC. Consult
your local Mitsubishi Electric representative.
Isolate the PLC and supply power to it using a different power
supply.
If the ERR LED turns OFF, noise may be affecting the PLC.
Take the following measures.
-
Check the ground wiring, and reexamine the wiring
route and installation location.
-
Fit a noise filter onto the power supply line.
If the ERR LED does not turn OFF even after the above
actions are taken, consult your local Mitsubishi Electric
representative.
Verify that extension cables are correctly connected.
Check user program.
The scan time exceeds the value stored in D8000.
When turning the power ON to the main unit, a 24V power
failure occurs in a powered extension unit. (The error occurs if
the 24V power is not supplied for 10 seconds or more after the
main power is turned ON.)
Action
inverter
communication,