Fx 2N; Fx -8Er (24V Dc Sink Input, Relay Output); Product Specifications - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
16.3
FX
-8ER (24V DC Sink Input, Relay Output)
2N

16.3.1 Product specifications

The generic specifications are identical to the main unit specifications.
For external wiring, refer to the following chapters.
1. Power supply specifications
Item
Product type
Rated voltage
2. Weight and Other specifications (External dimensions are described later.)
Item
MASS (Weight)
Other
3. Input specifications
Item
Input points
Connection type
Input form
Input signal voltage
Input signal current
Input impedance
ON input
sensitivity current
Input response time
Input signal form (Input sensor form)
Input circuit insulation
Indication of input operation
Input circuit diagram
254
24V DC (supplied from main unit and input/output powered extension unit)
The extension cable is already connected to the extension block.
Accessories: Label for indication of input/output number
The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Input ON current
Input OFF current
16 Input/Output Extension Blocks
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
→ Refer to Section 4.1 for generic specifications.
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
FX
-8ER
2N
FX
extension block
2N
FX
-8ER
2N
Approx. 0.2kg (0.44lbs)
FX
-8ER
2N
4 points
Vertical terminal block (M3 screws)
Sink
24V DC
10%
5mA/24V DC
4.3k
3.5mA or more at 24V DC
1.5mA or less
Approx. 10ms
No-voltage contact input
NPN open collector transistor
Photo-coupler insulation
LED on panel lights when input.
Sink input wiring
Main unit
S/S
0V
24V
24+
X
4.3k

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents