Mitsubishi Electric MELSEC-F FX3G Series User Manual page 50

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
4.
Specifications, External Dimensions and Terminal
Layout (Main Units)
This Chapter explains the specifications, external dimensions and terminal layout of the main units.
→ For the specifications for the input/output powered extension units, refer to Chapter 15.
4.1
Generic Specifications
Item
Ambient temperature 0 to 55 C (32 to 131 F) when operating and -25 to 75 C (-13 to 167 F) when stored
Ambient humidity
Vibration resistance
*1
Shock resistance
Noise resistance
Dielectric withstand
voltage
Insulation resistance
Grounding
Working atmosphere Free from corrosive or flammable gas and excessive conductive dust
Working altitude
Installation location
Overvoltage category ΙΙ or less
Pollution degree
*1.
The criterion is shown in IEC61131-2.
*2.
For more information on the dielectric withstand voltage test and the insulation resistance test of the
terminals of each product, refer to the following.
*3.
Ground the PLC independently or jointly.
Independent grounding
*4.
The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
*5.
The programmable controller is assumed to be installed in an environment equivalent to indoor.
44
→ For the specifications for the input/output extension blocks, refer to Chapter 16.
5 to 95%RH (no condensation) when operating
When installed on
*1
DIN rail
When installed
directly
2
147m/s
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
By noise simulator at noise voltage of 1,000Vp-p, noise width of 1 s, rise time of 1ns and period of 30 to 100Hz
1.5kV AC for one minute
500V AC for one minute
5M
or higher by 500 V DC insulation
resistance tester
Class D grounding (grounding resistance: 100
<Common grounding with a heavy electrical system is not allowed>
*4
< 2000m
*5
Inside a control panel
2 or less
Other
PLC
equipment
Best condition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
Specifications
Frequency(Hz)
Acceleration(m/s
10 to 57
-
57 to 150
4.9
10 to 57
-
57 to 150
9.8
Between each terminals and ground terminal
or less)
Other
PLC
equipment
Shared grounding
Good condition
4.1 Generic Specifications
2
Half amplitude(mm)
)
0.035
-
0.075
-
*2
*3
→ Refer to Subsection 4.1.1.
→ Refer to Section 9.3.
Other
PLC
equipment
Common grounding
Not allowed
Sweep Count for
X, Y, Z: 10 times
(80 min in each
direction)