Performance Specifications

The main unit performance specifications are explained below.
Operation control system
Input/output control system
Programming language
Program memory
Real-time clock
Kinds of
instructions
Processing
speed
Number of input/
output points
Input/output
relay
Auxiliary relay
State
Timer
(on-delay
timer)
Variable analog potentiometers
Counter
50
Item
Max. memory capacity/type
Memory cassette (Option)
Writing function during
running
Keyword function
*1
Clock function
Basic instructions
Applied instructions
Basic instructions
Applied instructions
(1)Extension-combined
number of input points
(2)Extension-combined
number of output points
(4)Remote I/O number of
points (CC-Link, AnyWireASLINK)
(3) + (4) total number of
points
Input relay
Output relay
For general
EEPROM keep
*2
For general
For special
For initial state
(EEPROM keep)
EEPROM keep
*2
For general
100ms
100ms
(for subroutine/interruption
subroutine)
10ms
1ms accumulating type
(EEPROM keep)
100ms accumulating type
(EEPROM keep)
1ms
16 bits up
(For general)
4 Specifications, External Dimensions and Terminal Layout (Main Units)
Stored program repetitive operation system with interruption function
Batch processing system (when END instruction is executed)
Input/output refresh instruction and pulse catch function are provided.
Relay symbol system + step-ladder system (SFC notation possible)
32000-step/EEPROM memory
Max. allowable write: 20,000 times
32000-step/EEPROM memory (with loader function)
Max. allowable write: 10,000 times
Provided (Program can be modified while the PLC is running.)
→ For the writing function during running, refer to Subsection 5.2.5.
With keyword/Customer keyword function
Built-in
1980 to 2079 (with correction for leap year)
2- or 4-digit year, accuracy within 45 seconds/month at 25 C
Sequence instructions: 29
Step-ladder instructions: 2
125 kinds
*3
Standard mode
: 0.21 s/instruction
*3
Extension mode
: 0.42 s/instruction
*3
Standard mode
: 0.5 s to several hundred s/instruction
*3
Extension mode
: 1.2 s to several hundred s/instruction
128 points or less
(3)Total points
128 points or less
The total number of remote I/O points in CC-Link and
128 points or less
AnyWireASLINK must be 128 points or less.
256 points or less
X000 to X177
The device numbers are octal.
Y000 to Y177
M0 to M383
384 points
M384 to M1535
1152 points
M1536 to M7679
6144 points
M8000 to M8511
512 points
S0 to S9
10 points
S10 to S999
990 points
S1000 to S4095
3096 points
T0 to T191
192 points
T192 to T199
8 points
T200 to T245
46 points
T246 to T249
4 points
T250 to T255
6 points
T256 to T319
64 points
Available as analog timers
VR1 : D8030
VR2 : D8031
C0 to C15
16 points
4.5 Performance Specifications
Performance
(1) + (2)
(3) total number of points is
128 or less.
-
-
-
-
-
-
-
0.1 to 3,276.7 sec
0.1 to 3,276.7 sec
0.01 to 327.67 sec
0.001 to 32.767 sec
0.1 to 3,276.7 sec
0.01 to 327.67 sec
Counting from 0 to 32,767