20.8.4 External wiring precautions

1. Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal
could cause burnout at the output element or the PCB.
To prevent this, a protection fuse should be inserted at the
output. Use a load power supply capacity that is at least 2
times larger than the total rated fuse capacity.
2. Transistor protection circuit for inductive loads
The transistor output circuit in the terminal block is
equipped with a Zener diode (50V) for protection.
When an inductive load is connected, however, a diode
should be connected parallel to the load when required.
The diode must comply with the specifications shown
below.
Reverse voltage
5 to 10 times of the load voltage
Forward current
Load current or more
3. Interlock
For loads such as forward/reverse contactors, etc., where
a hazardous condition could result if switched ON
simultaneously, an external interlock should be provided
for interlocking the PLC's internal programs as shown to
the right.
20.8 FX-16EYT-TB, FX-16EYT-H-TB
Load
0 to 7
Fuse
COMn
Terminal block
inductive
load
0 to 7
Fuse
COMn
Terminal block
Forward
limit
Interlock
Reverse
PLC output
limit
element
20 Terminal Block
11
12
13
14
Forward
15
Reverse
16
17
18
19
20
375

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents