10.2
24V DC input (Sink and source input type)
This section explains handling of 24V DC inputs in the main unit, precautions on input device connection, and
external wiring examples.

10.2.1 Handling of 24V DC input

1. Input terminals
Sink input
When a no-voltage contact or NPN open collector transistor
output is connected between an input (X) terminal and the 0V
terminal and the circuit is closed, the input (X) turns on.
Then, the input display LED lights.
Source input
When a no-voltage contact or PNP open collector transistor
output is connected between an input (X) terminal and the 24V
terminal and the circuit is closed, the input (X) turns on.
Then, the input display LED lights.
RUN terminal setting
X000 to X017 (up to the largest input number in the main unit
terminals by setting parameters.
*1.
X000 to X007 in the FX
2. Input circuit
Function of input circuit
The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is
provided with a C-R filter.
The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from
the input line.
There is a delay of approx. 10ms in response to input-switching from ON to OFF and from OFF to ON.
Change of filter time
X000 to X007 have digital filters, and the filter time can be changed in increments of 1ms in the range from 0
to 15ms through special data register (D8020). When 0 is specified for the time, the input filter values are set
as shown in the following table.
Input number
X000, X001, X003, X004
X002, X005, X006, X007
144
-14M
main unit, and X000 to X015 in the FX
3G
→ For the functions of the RUN terminals, refer to Subsection 14.2.1.
Input filter value when 0 is specified
10 s
50 s
10.2 24V DC input (Sink and source input type)
→ For the input specifications, refer to Section 4.3
*
*
*1
) of the main unit can be used as RUN input
3G
10 Input Wiring Procedures
Fuse
L
N
100 to 240V AC
S/S
0V
24V
X000
X001
X007
* Input impedance
Fuse
L
N
100 to 240V AC
S/S
0V
24V
X000
X001
X007
* Input impedance
-24M
main unit