Examples Of External Wiring (Source Input) [Ac Power Supply Type] - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition

10.2.4 Examples of external wiring (source input) [AC Power Supply Type]

Sink and source input type
Sink and source
input type
*1
Handle the power supply circuit correctly in accordance with Chapter 9 "Preparation for Wiring and
Power Supply Wiring Procedures."
*2
For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
*3
In the case of source input wiring, short-circuit the terminals of the extension units as well as
the S/S terminal and the 0V terminal of the main unit
*4
The "24V" and "0V" terminals are located on the output terminal side.
For details on the terminal layout, refer to Section 4.7.
Main unit
Input
impedance
5V 0V 24V
Input extension block
5V 0V 24V
Input / output powered extension unit
5V 0V 24V
Input extension block
5V 0V 24V
10.2 24V DC input (Sink and source input type)
L
N
Class D
grounding
*3
S/S
*4
0V
0V
24V
*4
24V
X0
X1
Input
terminal
S/S
X0
X1
Input
terminal
L
N
*3
S/S
0V
24V
X0
X1
Input
terminal
0V
24V
S/S
X0
X1
Input
terminal
10 Input Wiring Procedures
*1
Fuse
Three-
wire
sensor
Two-wire
proximity
sensor
*2
149
1
2
3
4
5
6
7
8
9
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents