End Stop Open: Set; Switch Compartment: Open - AUMA SQ 14.2 Operation Instructions Manual

Part-turn actuators with actuator controls
Hide thumbs Also See for SQ 14.2:
Table of Contents

Advertisement

SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1
9.2.2.

End stop OPEN: set

Information
9.3.

Switch compartment: open

3.
If the valve end position is not reached:
Slightly turn setting screw [4] counterclockwise until valve end position
CLOSED can be safely set.
Turning the setting screw [4] clockwise results in a smaller swing angle.
Turning the setting screw [4] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [4] clockwise to the stop.
This completes the setting of end stop CLOSED.
5.
Check O-ring in screw plug and replace if damaged.
6.
Fasten and tighten screw plug [3].
Having completed this procedure, the end position detection CLOSED can be set
immediately.
In general, the end stop OPEN does not have to be set.
1.
Remove screw plug [1].
2.
Move valve to end position OPEN with handwheel.
3.
If the valve end position is not reached:
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
Turning the setting screw [2] clockwise results in a smaller swing angle.
Turning the setting screw [2] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [2] clockwise to the stop.
This completes the setting of end stop OPEN.
5.
Check O-ring in screw plug and replace if damaged.
6.
Fasten and tighten screw plug [1].
Having completed this procedure, the end position detection OPEN can be set
immediately.
The switch compartment must be opened to perform the following settings (options).
Commissioning (basic settings)
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sq 05.2Sqr 05.2Sqr 14.2Matic am 01.1

Table of Contents