User Guide | Controller for appliance control, AK-CC55

Data

115 / 230 V AC (85-265 V). 5 VA, 50/60 Hz
Supply voltage
Power: Green LED
Sensor S2, S6
Pt 1000
Pt 1000 or PTC 1000 or Ntc5K or Ntc10K
Sensor S3, S4, S5
(All 3 must be of the same type)
PT 1000: -60 – 120 °C. +0.5 K
PTC1000: -60 – 80 °C. +0.5 K
NTC 5K: -40 – 80 °C. +1.0 K
Measuring of
NTC 10K: -40 – 120 °C. +1.0 K
temperature
Pt 1000 sensor
Ratiometric
Measuring of Pe
pressure transmitter
Measuring of RH
0-10 V
Display
LED, 3 digits
1 pc RJ12 output on compact versions and versions with
integrated displays
External display
2 pcs. RJ12 outputs on versions without displays
Max. 100m cable total
Signal from contact functions
Requirements to contacts: Gold plating
Digital inputs DI1,
Cable length must be max. 15 m
DI2
Use auxiliary relays when the cable is longer
Open loop: 12 V
Contact 3.5 mA
Digital inputs DI3 115 V / 230 V AC
Electrical cable
Max.1.5 mm
dimensions
DO1 (for AKV coil)
Solid state output
(DO3 and DO7 in
Multi Coil)
DO2, DO3, DO4
Relays*
DO5, DO6
Analogue output/
AO1
PWM
0 – 55 °C, During operations
-40 – 70 °C, During transport
Environments
20 – 80% Rh, not condensed
No shock influence / vibrations
Density
IP 20
Mounting
DIN-rail
Weight
0.4 Kg
Data
Fixed
communication
Extension option
Tx: Yellow LED
(Not for Compact version)
Rx: Green LED
Power reserve for
4 days
the clock
Approvals
EU Low Voltage Directive and EMC demands re CE-
marking complied with
LVD (2014/35/EU)
CB scheme acc. to IEC 60730-1 and 2-9
EMC (2014/30/EU)
EN 61000-6-2 and 6-3
Relays tested acc. to IEC 60079-15
* DO2 to DO6 are 16 A relays. Max. load must be observed. DO3 DO4 for
Compact and DO5 DO6 for Single / Multi Coil is recommended for EC Fan and
LED light.
All relays are sealed for use with flammable refrigerant like Propane R290.
Compliance with EN 60 335-2-89: 2010 Annex BB.
68 | BC308437742037en-000101
±0.3 K at 0 °C
±0.005 K per degree
10-90%
Ri > 10K ohm
Accuracy +/- 0,3% FS
multi-core cable
2
115V / 230 V AC
Max. 0.5 A
Max. 1 x 20 W AKV for 115 V AC
2 x 20 W AKV for 230 V AC
115 V / 230 V AC
Load max.: CE. 8 (6)A
UL. 8A res. 3FLA 18LRA
Load min.: 1VA
Inrush:
DO2 DO3 for Compact
DO5 DO6 for
Single/Multi Coil
TV-5 80A
0 / 10 V Pulse Width Modulated
(PWM) max. 15 mA.
0-10 V variable, max. 2 mA
MODBUS
Lon RS485
AK-CC55 Compact
AK-CC55 Single Coil
AK-CC55 Multi Coil
180
AK-CC55 Single Coil UI
AK-UI55 Set
AK-OB55
Can be installed on Single Coil and Multi Coil versions.
60
© Danfoss | DCS (vt) | 2019.09