10. Technical Data - Danfoss ThermoControl-3 Mounting Manual

Table of Contents

Advertisement

Mounting Guide

10. Technical data

Inputs
Outputs
Operating voltage (V)
Current consumption
Ambient temperature
Protection class
Protection class
Interference emission
Resistance to interference
Dimensions
Weight
12
DEN - SMT / PL
ThermoControl – 3
8 x Pt1000 two-wire sensors
1 x potential-free circuit for external disinfection
1 x potential-free circuit for temperature regulator (TR)
4 x potential-free circuits for pump fault inputs
1 x frequency input for flow sensor
3 x 3-point signal maximum load 230V AC, 2A
4 x pump power supplies, switched: maximum load 230V AC, 2A
4 x pump control signals PWM 5V level (100Hz)
4 x pump control signals 0-10V DC, input resistance > 100kΩ
including four switch outputs (on/off ) 5V level
1 x heat request, potential-free two-way contact, maximum load
230V AC, 2A
1 x fault message output, potential-free two-way contact, maximum load
230V AC, 2A
1 x 12V DC: maximum load 50mA
230V ±10%, 50-60Hz
max. 6.3A
0-40°C
IP 54
II as per VDE 0106
as per EN 61000-6-3
as per EN55011 + A1 : class B
as per EN 61000-6-2
(height x width x depth): 159 x 248 x 124 mm
1.6 kg
VM.GU.A1.02
Danfoss District Energy