User Guide | Controller for appliance control, AK-CC55

Data communication

The controller has built-in MODBUS data communication.
If there is a requirement for a different form of data
communication, a Lon RS 485 module can be inserted in the
controller.
The connection must then be to the module.
(This option is not available in the compact version).
Display
The controller has one or two plugs for an external display. One of
the following display types can be connected to a plug:
• AK-UI55 Info (temperature display)
• AK-UI55 Set (temperature display and operation)
• AK-UI55 Bluetooth (temperature display and app operation).
The connection between the display and the controller must be
made using an AK-UI55 cable.
The distance between the controller and the display must not
exceed 100 m.
If there are two external displays, it will be the sum of the two
distances that cannot exceed 100 m.

Override

The controller contains a number of functions which can be used together with the override function in the master gateway/system
manager:
Function via data communication
Start of defrosting
Coordinated defrost
Prevent defrost start
Day/Night schedule
Light control
Forced closing
Forced cooling
Rail heat link to dew point
P0 optimization
Adaptive defrost
Adaptive liquid control
where fluid flow is allowed
Case shutdown
Locking operation via bluetooth
46 | BC308437742037en-000101
Function in gateway/system manager
Defrost control / Time schedule / Defrost
group
Defrost control / Defrost group
Day/Night control / Time schedule / Light
zone
Day/Night control / Time schedule
Forced Close / Injection ON / AKC ON
/ Enhanced rail heat
P0 Optimization
/ Adaptive defrost. System manager only
Customized control in AK-SM 8xx
On/off + Boolian logic function in AK-SM 720
Customized control in AK-SM 8xx + Boolian
logic function in AK-SM 720
Used parameters in the controller
--- Def start
--- HoldAfterDef / - - - DefrostState
--- Disable Def
--- Night setback
O39 light Remote
--- Forced close
--- Forced cool
--- Act.DewPoint
The controller supports P0 optimization
- - - Tc TempMean, MC Def.start
- - - MC Liq. Ctrl
- - - Case shutdown
- - - BT lock