User Guide | Controller for appliance control, AK-CC55

Service

Operating status. Please refer to the overview on page 62
Temperature measured with S5 sensor
Status on DI1 input. on/1=closed
Read the duration of the ongoing defrost or the duration of the last completed
defrost
Temperature measured with S3 sensor
Status at the day-/night operation (night operation: on/off )
Temperature measured with S4 sensor
Thermostat temperature
Read the ongoing cut-in time for the thermostat or the duration of the last com-
pleted cut-in
Read the temperature at the S2 evaporator outlet sensor
Read superheat
Read superheat reference
Opening degree of AKV valve
Read the evaporating pressure
Read the evaporating temperature
Read the temperature at the S6 sensor
Status on DI2 input. on/1=closed
Readout display 1 value
Readout of alarm air temp. Section A
* Status on relay for compressor/solenoid valve
* Status on relay for fan
* Status on relay for defrost
* Status on relay for rail heat
* Status on relay for alarm
* Status on relay for light
* Status on relay for valve in suction line
* Status on relay for compressor 2
* Temperature measured with S5B sensor
* Temperature measured with S3B sensor
* Status on relay for hot gas
* Status on relay for night blinds
* Status on relay for defrost B
* Status on relay for heat function
* Readout of the actual rail heat effect in %
Readout of which thermostat used for regulation: 1= Thermostat 1,
2= Thermostat 2
Status on input DI3 (on/1 = 230 V)
Readout of thermostat band in use
Readout of the actual cut-out value for the thermostat
Status on function "Adaptive defrost"
0: Off. Function is not activated and is zero-set
1: Sensor error S3/S4 are reversed.
2: Tuning is in progress
3: Normal
4: Light build-up of ice
5: Medium build-up of ice
6: Heavy build-up of ice
Readout
of the current Brine PWM OD in %
Number of defrosts carried out since the initial power up or since the resetting of
the function
Number of defrosts skipped since the initial power up or since the resetting of the
function
*) Not all will be displayed. Only the function belonging to the selected application is displayed.
60 | BC308437742037en-000101
Service
u00
Ctrl. state
u09
S5 temp.
u10
DI1 status
u11
Defrost time
u12
S3 air temp
u13
Night Cond.
u16
S4 air temp
u17
Ther. air
u18
Ther runtime
u20
S2 temp.
u21
Superheat
u22
SH ref.
u23
AKV OD %
u25
Evap.press Pe
u26
Evap.temp Te
u36
S6 temp
u37
DI2 status
u56
Display air
u57
Alarm air
u58
Comp1/LLSV
u59
Fan relay
u60
Def. relay
u61
Railh. relay
u62
Alarm relay
u63
Light relay
u64
SuctionValve
u67
Comp2 relay
u75
S5 temp. B
u76
S3 temp. B
u80
Hotgas valve
u82
Blinds relay
u83
Def. relay B
u84
Heat relay
u85
Rail DutyC %
u86
Ther. band
u87
DI3 status
u90
Cutin temp.
u91
Cutout temp.
U01
AD state
U02
Pwm OD %
U10
Acc.defrost
U11
Acc.def.skip