User Guide | Controller for appliance control, AK-CC55
Multi Coil - continued
Humidity
Setpoint for cut-in of humidity function
Difference for humidity function
Alarm limit for high humidity (too damp)
Alarm limit for low humidity (too dry)
Delay time for a humidity alarm
Humidity function during defrosting
Setpoint for RH% at input signal on 0 V
Setpoint for RH% at input signal on 10 V
Use humidity control
Miscellaneous
Delay of output signals after power failure
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open.
3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main
switch. 6=night operation. 7=thermostat band changeover (activate
r21). 8=alarm function when closed. 9=alarm function when open.
10=Appliance cleaning (pulse signal). 11=forced cooling at hot gas
defrost. 12=Open night cover. 14=Refrigeration stopped (forced
closing). 15=case shutdown. 16=light. 20=Refrigerant alarm. 21=
adaptive liquid control when short-circuited.
Network address
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at Lon 485)
Access code 3 (all settings)
Used sensor type: 0=Pt1000, 1=PTC1000, 2=Ntc5K, 3=Ntc10K.
(S2 is not affected. It is always Pt1000 ohms)
Max. hold time after coordinated defrost
Pressure transmitter working range – min. value
Pressure transmitter working range – max. value
Refrigerant setting:
1=User defined. 3-digits. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13.
7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b.
13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A.
19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A.
31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A.
37=R407F. 38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A.
42=R452A. 43=R450A. 45=R454B. 46=R1233zdE. 47=R1234zeZ.
48=R449B. 49=R407H
Input signal on DI2. Function:
0=not used. 1=status on DI2. 2=door function with alarm when
open. 3=door alarm when open. 4=defrost start (pulse signal). 5=ext.
main switch. 6=night operation. 7=thermostat band changeover
(activate r21). 8=alarm function when closed. 9=alarm function
when open. 10=Appliance cleaning (pulse signal). 11=forced cooling
at hot gas defrost. 12=Open night cover. 13=coordinated defrost.
14=Refrigeration stopped (forced closing). 15=case shutdown.
16=light. 20=Refrigerant alarm. 21= adaptive liquid control when
short-circuited.
Configuration of light function: 1=Light follows day /night operation,
2=Light control via data communication via 'o39' , 3=The light is
controlled with a door switch on a DI input, 4=As "2", but light
switches on and night cover will open if the network cuts out for more
than 15 minutes, 5=Light controlled via a DI input.
Activation of light relay (only if o38=2) On=light
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat cycle time (On time + Off time)
© Danfoss | DCS (vt) | 2019.09
R-W
Code
1
2 3
4
0-2
h23
1
1-2
h24
1
1-2
h25
1
1-2
h26
1
1-2
h27
1
1-2
h28
1
1-2*
h29
1
1-2*
h30
1
1-2*
h31
1
1-2
o01
1
1
1
1
1-2*
o02
1
1
1-3*
o03
1
1
1
1
1-2
o04
1
1
1
1
3-3
o05
1
1
1
1
1-3*
o06
1
1
1
1
1-2
o16
1
1
1
1
1-3*
o20
1
1
1
1
1-3*
o21
1
1
1
1
1-3*
o30
1
1
1
1
1-2*
o37
1
1
1
1
1-2
o38
1
1
1
1
1-2
o39
1
1
1
1
1-2
o41
1
1
1
1
1-2
o42
1
1
1
1
1-2
o43
1
1
1
1
5
Min.
Max.
Fac.
0 %
100 %
70
1 %
30 %
5
0 %
100 %
100
0 %
100 %
0
0 min.
240 min.
60
0/Off
1/On
0/Off
0 %
"h30"
0
"h29"
100 %
100
0/Off
1/On
0/Off
1 0 sec
600 sec
5
0
21
0
1 0
240
0
1 0/Off
1/On
0/Off
1 0
999
0
1 0/Pt
3/N10
0/Pt
1 0 min.
360 min.
20
1 -1 bar
5 bar
-1
1 6 bar
200 bar
12
1 0
42
0
1 0
21
0
1 1
5
1
1 0/Off
1/On
0/Off
1 0 %
100 %
100
1 0 %
100 %
100
1 1 min.
60 min.
5
BC308437742037en-000101 | 35