Power Supply
Supply Requirements
Requirements
Power
Power
Supply
Requirements
Improper wiring may cause electric shock or other
serious injury if work is not performed properly.
All electrical wiring must be done by a qualified
electrician and comply with all local codes and
regulations.
Table 1 1 1 . . . Power
Power Supply
Supply Specifications
Table
Table
Power
Supply
Model
Model
Model
Voltage
Voltage
Voltage
Phase
Phase Hz
Phase
ECx9xx
200–240
1
ECx0xx
Vac
ECxJxx 380–480
3
Vac
3A3453H
Specifications
Specifications
Hz
Hz
Power
Power
Power
50/60
5.8 kVA (2.9
kVA per motor)
50/60
6.0 kVA (3.0
kVA per motor)
Hazardous Area
Area Cabling
Cabling and
Hazardous
Hazardous
Area
Cabling
Requirements
Requirements
Requirements
Explosion Proof
Proof
Explosion
Explosion
Proof
All electrical wiring in the hazardous area must be
encased in Class I, Division I, Group D approved
explosion-proof conduit. Follow all National, State,
and Local electric codes.
A conduit seal (D) is required within 18 in. (457
mm) of the motor for the US and Canada. See
Typical Installation, page
All cables must be rated at 70°C (158°F).
Flame
Flame Proof
Flame
Proof (ATEX)
Proof
(ATEX)
(ATEX)
Use appropriate conduit, connectors, and cable
glands rated for ATEX II 2 G. Follow all National,
State, and Local electric codes.
All cable glands and cables must be rated at 70°C
(158°F).
Installation
and Conduit
Conduit
and
Conduit