Operation
Setup Screen
Screen 8 8 8
Setup
Setup
Screen
Use this screen to set up the pressure for transducer
1. Selecting a transducer and checking the pressure
control checkbox activates closed loop pressure
control.
Figure 37 Setup Screen 8
Setup
Setup Screen
Setup
Select from the dropdown options to
enable the transducer.
Enables the pump to use the transducer
to control to a pressure setpoint
(psi/bar/mpa, rather than %force)
Enter the calibration scale factor from the
transducer label.
Enter the calibration offset value from the
transducer label.
Displays the current transducer reading.
Figure 38 Select Pressure Transducer
36
Screen 8 8 8
Screen
Figure 39 Closed Loop Pressure Enable
Figure 40 Enter Calibration Scale Factor
Figure 41 Enter Calibration Offset Value