Beckhoff EL6731 Documentation page 159

Master/slave terminal for profibus
Table of Contents

Advertisement

Index F920 AoE Settings
Index (hex) Name
F920:0
AoE Settings
F920:01
Local AoE Net ID
* These parameters depend on the baud rate; the following table shows the default values for the respective
baud rate:
Data_rate
Tsl
max.
Tsdr
9 (12 Mbaud) 1000
800
8 (6 Mbaud)
600
450
7 (3 Mbaud)
400
250
6 (1.5 Mbaud) 300
150
4 (500 kbaud) 200
100
3 (187.5
150
100
kbaud)
2 (93.75
150
100
kbaud)
1 (19.2 kbaud) 150
100
0 (9.6 kbaud) 150
100
EL6731
Meaning
Max. subindex
Local AoE Net ID
Tqui
Tset
Ttr
max_retry_limit
9
16
12000
4
6
8
12000
3
3
4
12000
2
0
1
12000
1
0
1
12000
1
0
1
12000
1
0
1
12000
1
0
1
12000
1
0
1
12000
1
Version: 2.8
EtherCAT communication EL6731-00x0
Data type
UINT8
OCTET-
STRING[6]
Min_Slave_Interval
Data_Con-
trol_Time
10
1
20
2
40
4
80
8
200
20
400
40
800
80
4000
400
8000
800
Flags
Default
RO
0x01 (1
)
dec
RO
{0}
Max
Retry
(DX)
4
3
2
1
1
1
1
1
1
159