Index F102 DP Slave Status data
Index
Name
F102:0
DP Slave Status data This object contains the status of communication to the
F102:01
...
F102:7D
Index F10F Cycle Statistic data
Index (hex) Name
F10F:0
Cycle Statistic data
F10F:01
Multiplier
F10F:02
Divider
F10F:03
Cycle Time
F10F:04
Cycle Distance Time
F10F:05
Output Calc And
Copy Time
F10F:06
Input Calc And Copy
Time
F10F:07
Output Delay Time
F10F:08
SM/SYNC Event Dis-
tance Time
EL6731
Meaning
DP slaves that is mapped to TxPDO 133 (index 0x1A84
[} 147])
Communication status of the first configured DP slave (in
the objects 0x8000 [} 154], 0x8001 [} 155], 0x8002
[} 155])
0
Slave is exchanging data; DP inputs are up to date
1
Slave is deactivated (via AoE)
2
Slave does not respond
3
slave currently exchanging data with another mas-
ter
4
incorrect slave response (e.g. service not activated
in the case of data exchange)
5
Slave reports parameterization error (error in the
SetPrm telegram (usually Ident-Number or User-
PrmData))
6
Slave reports that a DP function is not supported
7
Slave reports configuration error 8 - error in the
ChkCfg telegram (usually incorrect DP module con-
figured))
8
Slave is in DP bootup but is not yet ready for data
exchange
9
Slave reports static diagnosis
11
Response with bus error (e.g. parity or checksum
error)
14
Response with telegram error (e.g. request bit set)
15
Slave reports no resources (e.g. PrmData or Cfg-
Data is too long)
16
Slave reports that the DP service is not activated
17
Unexpected telegram received (e.g. token when
waiting for a response from a slave)
18
Slave is ready for data exchange; however, no
process data are exchanged over EtherCAT as yet
Communication status of the mth configured DP slave
Meaning
This object contains the measured times of the respec-
tive last cycle. They can be transferred cyclically with Tx-
PDO 135 (0x1A86 [} 148]) or TxPDO 136 (0x1A87
[} 148]) and they then always contain the values for the
preceding cycle.
The entries 0xF10F:03, 0xF10F:04, 0xF10F:05 and
0xF10F:06 must be multiplied by this value in order to
convert these entries into the unit 100 ns
The entries 0xF10F:03, 0xF10F:04, 0xF10F:05 and
0xF10F:06 must be divided by this value in order to con-
vert these entries into the unit 100 ns
Cycle time (0x1C32:05 [} 150]) of the preceding DP cycle
in local ticks
Distance between the last two SM2 events (only if
0x1C32:01 [} 150] = 1 or 0x1C32:01 = 2)
Output Calc And Copy Time (0x1C32:06 [} 150]) of the
preceding DP cycle in local ticks
Input Calc And Copy Time (0x1C33:06) of the preceding
DP cycle in local ticks
Output Delay Time (0x1C32:09 [} 150]) of the preceding
cycle in ns
SM/SYNC0 Event Distance Time (distance between SM2
and SYNC0 event) of the preceding cycle in ns (must be
activated via register 0x816 in the ET1100).
Version: 2.8
EtherCAT communication EL6731-00x0
Data type
Flags
UINT8
RO
UINT8
RO
UINT8
RO
Data type
Flags
UINT8
RO
UINT16
RO
UINT16
RO
UINT16
RO
UINT16
RO
UINT16
RO
UINT16
RO
UINT32
RO
INT32
RO
Default
Default
0x08 (8
)
dec
0x0000 (0
)
dec
0x0000 (0
)
dec
0x0000 (0
)
dec
0x0000 (0
)
dec
0x0000 (0
)
dec
0x0000 (0
)
dec
0x00000000
(0
)
dec
0x00000000
(0
)
dec
157

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El6731 seriesEl6731-0000El6731-0010

Table of Contents