Beckhoff EL6731 Documentation page 128

Master/slave terminal for profibus
Table of Contents

Advertisement

Parameterization and commissioning
Error code
Meaning
0x214E
DPV1-C2-Read: MSAC_C2 is not activated
0x214F
DPV1-C2-Write: MSAC_C2 is not activated
0x2150
DPV1-C2-DataTransport: MSAC_C2 is not activated
0x2151
DPV1-C2-Read: FDL fault (no response etc.)
0x2152
DPV1-C2-Read: connection aborted
0x2153
DPV1-C2-Read: DPV1 fault (4 bytes error code in the diagnostic data of the slave)
0x2154
PKW-ReadNoOfElements: length must equal 1
0x2155
PKW-ReadNoOfElements: PKW is not activated
0x2156
PKW-ReadNoOfElements: axis number is too great
0x2157
PKW-ReadNoOfElements: slave not in data exchange
0x2158
PKW-ReadNoOfElements: unknown AK received (6 or 7 expected)
0x215A
DPV1-C2-Write: FDL fault (no response etc.)
0x215B
DPV1-C2-Write: connection aborted
0x215C
DPV1-C2-Write: DPV1 fault (4 bytes error code in the diagnostic data of the slave)
0x215D
DPV1-C2-DataTransport: FDL fault (no response etc.)
0x215E
DPV1-C2-DataTransport: connection aborted
0x215F
DPV1-C2-DataTransport: DPV1 fault (4 bytes error code in the diagnostic data of the slave)
0x2163
DPV1-C2-DataTransport: Incorrect IndexOffset
0x2600-0x26F
AK 7 (error) during PKW processing, error code in low byte
F
0x2700-0x27F
Fault during DPV1 processing, 4 bytes error code in the slave diagnostic data, byte 3 of the error code (error class) is in
F
Low byte
"Not expected" error codes from the PROFIBUS slave in 0x28xx
Error code
Meaning
0x0
OK (is usually not passed on by the terminal)
0x1
UE = User Error
0x2
RR = No resources
0x3
RS = SAP not enabled
0x8***
DL = Data Low (normal case with DP)
0x9***
NR = No response data ready
0xA
DH = Data High (DP diagnosis pending)
0xC
RDL = Data not received and Data Low
0xD
RDH = Data not received and Data High
***)
DL and NR are handled by the EL6731
128
Version: 2.8
EL6731

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El6731 seriesEl6731-0000El6731-0010

Table of Contents