Assembly guidelines

5.1.12 Mounting clearances

5.1.13 Ground connection for configurations which are not isolated

5.1.14 Air guidance

5.1.15 Power loss in the cabinet

5.1.16 Power supply

5-8
 Non-damped contactors may not be used in a cabinet with FM
components.
 If non-damped contactors are used in a cabinet then adjacent
cabinets must be separated by a metal partition.
 Each cabinet in which S7-400 components are installed/mounted
must have a screen rail. Serrated rails are suitable. The screen rail
must be connected directly to the cabinet frame.
 No gas discharge lamps may be used in the cabinet.
 The screens of incoming cables must be connected directly to the
screen rail.
 The cabinets must be designed so that air can circulate freely within
them.
For additional information refer to Installation Manual „S7-400 and
M7-400 Programmable Controllers Hardware and Installation".
For additional information refer to Installation Manual „S7-400 and
M7-400 Programmable Controllers Hardware and Installation".
For additional information refer to Installation Manual „S7-400 and
M7-400 Programmable Controllers Hardware and Installation".
For additional information refer to Installation Manual „S7-400 and
M7-400 Programmable Controllers Hardware and Installation".
For additional information refer to Installation Manual „S7-400 and M7-
400 Programmable Controllers Hardware and Installation".
In order to diminish the effects of noise and disturbances, a line filter
should be provided for the 24V DC power supply of the binary inputs and
outputs (e.g. line filter SIFI-B, Order No. B84112-B-.... from Epcos/line
filter NF 1-1 from Phönix Contact). This should be located as close as
possible to the terminal block. The shield connection of the line filter must
be connected to ground through the shortest possible distance.
Application Module FM 458-1 DP - User Manual