The Private page should now be visible and the Calibration page is the first sub
5.
page as shown in Figure 7-40.
Figure 7-40 The Calibration Screen
6.
Before starting calibration the handler and certain storage array maga-
zine rows must be emptied of any tape cartridges. Please look at the li-
braries control panel for instructions detailing exactly which rows
must be emptied for individual models.
After the tape cartridges have been removed press the Calibrate button to begin
7.
the calibration process, which may take several minutes to complete.
After the libraries have successfully been calibrated the current password
8.
should be cleared (removed) to prevent unauthorized access to the private
screens.
7-40
Field–Replaceable Units (FRUs)
511010 Rev. 07-01-19