6.7.2
Adjustable parameters
Introduction
For information on programming analog modules, refer to the chapter
modules
Parameters
Table 6-20
Overview of parameters for SM 331; AI 8 x 12 bit
Parameters
Enable
Diagnostic interrupt
•
Hardware interrupt when
•
limit exceeded
Hardware interrupt trigger
High limit
•
Low limit
•
Diagnostics
Group diagnostics
•
with wirebreak monitoring
•
Measurement
Measuring method
•
Measuring range
•
Noise suppression
•
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.7 Analog input module SM 331; AI 8 x 12 Bit;(6ES7331-7KF02-0AB0)
.
Range of values
Yes/no
Yes/no
May be restricted by the measuring range
from 32511 to - 32512
from - 32512 to 32511
Yes/no
Yes/no
disabled
V voltage
4DMU current (4-wire transducer)
2DMU current (2-wire transducer)
R-4L resistance (4-wire connection)
RTD-4L thermoelectric resistance
(linear, 4-wire connection)
TC-I thermocouple
(internal comparator)
TC-E thermocouple
(external comparison)
TC-IL thermocouple
(linear, internal comparator)
TC-EL thermocouple
(linear, external comparison)
Measuring methods and ranges
See table
400 Hz; 60 Hz; 50 Hz; 10 Hz
Programming analog
Default
Parameter
type
No
Dynamic
No
-
Dynamic
No
static
No
V
Dynamic
± 10 V
50 Hz
Analog modules
Scope
Module
Channel
Channel
group
Channel or
channel
group
6-59