Measuring ranges
Program the measuring ranges in
Table 6-41
Selected measuring method
V: Voltage
R-4L: resistance (4-wire connection)
RTD-4L: Thermoelectric resistance
(linear, 4-wire connection)
(temperature measurement)
Output ranges of SM 334; AI 4/ AO 2 x 12 bit
The "voltage" output type and "0 V to 10 V" output range are set by default at the module.
You can always use this combination of the output type and range without having to program
the SM 334; AO 4 x 2 Bit in
Table 6-42
Selected type of output
Voltage
See also
Representation of the analog values of analog output channels (Page 5-18)
6.16.3

Additional information to SM 334; AI 4/ AO 2 x 12 bit

Unused channels
Set the "disabled" argument at the "measuring method" parameter for unused input
channels. This reduces the module's cycle time.
Always short-circuit unused input channels, and connect these to M
interference immunity of the analog input module.
To take the unused output channels of SM 334; AI 4/AO 2 x 12 Bit off power, always set
"disabled" argument at the "output type" parameter, and leave the connection open.
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.16 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0)
STEP 7
Measuring methods and ranges
STEP 7
Output ranges
.
Measuring range
0 V to 10 V
10 kΩ
Pt 100 Klima
.
Output range
0 V to 10 V
Analog modules
. This optimizes
ANA
6-145