Line protection
The mains supply of the PS 305 power supply module (2 A) should be protected with a
miniature circuit-breaker (for example Siemens 5SN1 series) of the following rating:
● Rated current at 110 VDC: 10 A
● Tripping characteristics (type): C.
Reaction to atypical operating conditions
Table 2-1
Reaction of the PS 305;(2 A) power supply module to atypical operating conditions
If ...
... the output circuit is overloaded:
I > 3.9 A (dynamic)
3 A < I ≤ 3.9 A (static)
... short-circuit at the output
overvoltage on primary side
undervoltage on primary side
Technical data of PS 305; 2 A (6ES7305-1BA80-0AA0)
Technical data
Dimensions and weight
Dimensions W x H x D (mm)
Weight
Input parameters
Input voltage
Rated value
Voltage range
Rated input current
at 24 V
at 48 V
at 72 V
at 96 V
at 110 V
Inrush current (at 25 °C)
I
t (at inrush current)
2
Output parameters
Output voltage
Rated value
Permissible range
Rampup time
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
2.1 Power Supply Module PS 305; 2 A; (6AG1305-1BA80-0AA0)
... then ...
Voltage dip, automatic voltage recovery
Voltage drop, reduction of service life
Output voltage 0 V; automatic voltage recovery
after short-circuit is eliminated
risk of destruction
Automatic shut-down; automatic voltage
recovery
80 x 125 x 120
approx. 740 g
24/48/72/96/110 VDC
16.8 VDC to 138 VDC
2.7 A
1.3 A
0.9 A
0.65 A
0.6 A
20 A
5 A
s
2
24 VDC
24 V ± 3 %, open circuit-proof
max. 3 s
Power supply modules
24 VDC LED
flashes
off
-
off