Siemens SIMATIC S7-300 Manual page 344

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Analog modules
6.12 Analog output module SM 332; AO 4 x 16 bit; isochronous; (6ES7332-7ND02-0AB0)
Technical data
Technical data
Dimensions and weight
Dimensions W x H x D (mm)
Weight
Module-specific data
Isochronous mode supported
Support of CiR
Reaction of non-programmed outputs
Number of outputs
Cable length
shielded
Voltages, currents and potentials
Rated load voltage L+
Reverse polarity protection
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
between channels
Permissible potential difference
Between outputs (ECM)
between M
and M
ANA
Isolation test voltage
Current consumption
from the backplane bus
from load voltage L+ (no-load)
Power loss of the module
Formation of analog values
Resolution (including sign)
± 10 V
0 V to 10 V
1 V to 5 V
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
Conversion time (per channel)
in standard operation
in isochronous mode
Basic execution time of the module (independent of the number of
enabled channels)
in standard operation
in isochronous mode
6-110
(V
)
internal
ISO
40 x 125 x 117
approx. 220 g
Yes
Yes
return the last valid output value before the
parameterization
4
max. 200 m
24 VDC
Yes
Yes
Yes
Yes
200 VDC / 120 VAC
200 VDC / 120 VAC
1500 VDC
max. 120 mA
max. 290 mA
typ. 3 W
16 bits
15 bits
14 bits
16 bits
15 bits
15 bits
<200 μs
640 µs
<800 μs
750 µs
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04

Hide quick links:

Advertisement

Table of Contents
loading