Technical data
Basic error limit (operational error limit at 25 °C, relative to input range)
Voltage input
•
Current input
•
Temperature error (relative to input range)
Linearity error (relative to input range)
Repetition accuracy (in transient state at 25 °C, relative to input
range)
Output ripple; range 0 Hz to 50 kHz (relative to output range)
Noise suppression, error limits of outputs
Crosstalk between outputs
Operational limit (across the temperature range, relative to output range)
Voltage output
•
Current output
•
Basic error limit (operational error limit at 25 °C, relative to output range)
Voltage output
•
Current output
•
Temperature error (relative to output range)
Linearity error (relative to output range)
Repetition accuracy (in transient state at 25 °C, relative to output
range)
Output ripple (bandwidth relative to output range)
Status, interrupts, diagnostics
Interrupts
Diagnostics functions
Transducer selection data
Input ranges (rated values) / input impedance
Voltage
•
Current
•
Permissible voltage at voltage input (destruction limit)
Permissible current at current input (destruction limit)
Wiring signal transducers
for voltage measurement
•
for current measurement
•
as 2-wire transducer
as 4-wire transducer
Actuator selection data
Output ranges (rated values)
Voltage
•
Current
•
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.15 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
± 0,7 %
± 0,6 %
± 0.005 %/K
± 0,05 %
± 0,05 %
± 0,05 %
> 40 dB
± 0,6 %
± 1,0 %
± 0,5 %
± 0,5 %
± 0.02 %/K
± 0,05 %
± 0,05 %
± 0,05 %
None
None
0 V to 10 V/100 k Ω
0 mA to 20 mA/50 Ω
max. 20 V continuous; 75 V for max. duration of 1 s
(duty factor 1:20)
40 mA
with 20-pin front connector
supported
supported with external
supply
0 V to 10 V
0 mA to 20 mA
Analog modules
6-135