Technical data
Basic error limit (operational error limit at 25 °C, relative to input range)
Voltage input
Current input
Temperature error (relative to input range)
Linearity error (relative to input range)
Repetition accuracy (in transient state at 25 °C, relative to input
range)
Output ripple; range 0 Hz to 50 kHz (relative to output range)
Noise suppression, error limits of outputs
Crosstalk between outputs
Operational limit (across the temperature range, relative to output range)
Voltage output
Current output
Basic error limit (operational error limit at 25 °C, relative to output range)
Voltage output
Current output
Temperature error (relative to output range)
Linearity error (relative to output range)
Repetition accuracy (in transient state at 25 °C, relative to output
range)
Output ripple (bandwidth relative to output range)
Status, interrupts, diagnostics
Interrupts
Diagnostics functions
Transducer selection data
Input ranges (rated values) / input impedance
Voltage
Current
Permissible voltage at voltage input (destruction limit)
Permissible current at current input (destruction limit)
Wiring signal transducers
for voltage measurement
for current measurement
as 2-wire transducer
as 4-wire transducer
Actuator selection data
Output ranges (rated values)
Voltage
Current
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.15 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
± 0,7 %
± 0,6 %
± 0.005 %/K
± 0,05 %
± 0,05 %
± 0,05 %
> 40 dB
± 0,6 %
± 1,0 %
± 0,5 %
± 0,5 %
± 0.02 %/K
± 0,05 %
± 0,05 %
± 0,05 %
None
None
0 V to 10 V/100 k Ω
0 mA to 20 mA/50 Ω
max. 20 V continuous; 75 V for max. duration of 1 s
(duty factor 1:20)
40 mA
with 20-pin front connector
supported
supported with external
supply
0 V to 10 V
0 mA to 20 mA
Analog modules
6-135