Sm 338; Pos-Input Programming - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Note
The Freeze function is acknowledged automatically when you assign new parameters with
different arguments to the relevant
channel.
The freeze function remains unaffected if you set parameters with identical arguments.
See also
SM 338; POS-INPUT addressing (Page 7-16)
SM 338; POS-INPUT programming (Page 7-15)
7.4.3

SM 338; POS-INPUT programming

Programming
You program the SM 338; POS-INPUT in
CPU is in STOP mode.
After you completed the parameter declaration, download the parameters from the PG to the
CPU. At its next STOP → RUN transition, the CPU transfers the parameters to the SM 338.
New parameters can not be assigned by the user program.
Parameters of SM 338; POS-INPUT
The table below provides an overview of configurable parameters and defaults for the SM
338.
The defaults apply if you have not set any parameters in
Table 7-3
Parameters of SM 338; POS-INPUT
Parameters
Enable
Fast-Mode
Enable
Diagnostic interrupt
Absolute value encoder (SSI)
1)
Code type
1)
Transmission rate
1) ,3)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
7.4 Position decoder module SM 338; POS-INPUT; (6ES7338-4BC01-0AB0)
Range of values
Yes / no
Yes / no
none; 13 bits; 21 bits; 25 bits
Gray; Binary
125 kHz; 250 kHz; 500 kHz; 1 MHz
STEP 7
. Always program the module while the
STEP 7
Note
Enable parameter.
Applies to all 3 channels.
Enable parameter.
Applies to all 3 channels.
none: The encoder input is switched
off.
Code returned by the encoder.
Data transfer rate of the SSI position
detection. Observe the relationship
between cable lengths and the
transmission rate (see Technical data)
Other signal modules
(default setting bold).
7-15