Advertisement

Table 5-7
Representation of analog values in the 1 V to 5 V and 0 V to 10 V voltage measuring ranges
System
Voltage measuring range
dec
hex
1 to 5 V
32767
7FFF
5.741 V
32512
7F00
32511
7EFF
5.704 V
27649
6C01
27648
6C00
5 V
20736
5100
4 V
1
1
1 V + 144.7 µV
0
0
1 V
-1
FFFF
-4864
ED00
0.296 V
-4865
ECFF
-32768
8000
Representation of analog values in the current measuring ranges
Table 5-8
Representation of analog values in the ±3.2 mA to ±20 mA current measuring ranges
System
Current measuring range
dec
hex
±20 mA
32767
7FFF
23.70 mA
32512
7F00
32511
7EFF
23.52 mA
27649
6C01
27648
6C00
20 mA
20736
5100
15 mA
1
1
723.4 nA
0
0
0 mA
-1
FFFF
-20736
AF00
-15 mA
-27648
9400
-20 mA
-27649
93FF
-32512
8100
-23.52 mA
-32513
80FF
-32768
8000
-23.70 mA
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
0 to 10 V
11.852 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
Negative values are not
supported
±10 mA
±3.2 mA
11.85 mA
3.79 mA
11.76 mA
3.76 mA
10 mA
3.2 mA
7.5 mA
2.4 mA
361.7 nA
115.7 nA
0 mA
0 mA
-7.5 mA
-2.4 mA
-10 mA
-3.2 mA
-11.76 mA
-3.76 mA
-11.85 mA
-3.79 mA
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
5-5