Siemens SIMATIC S7-300 Manual page 163

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Technical data
Transducer selection data
Input voltage
Rated value
for "1" signal
for "0" signal
Input current
with "1" signal
Input delay
at "1" to "0"
at "1" to "0"
Input characteristics
Connection of 2-wire BEROs
Permissible quiescent current
Wiring signal transducers
Actuator selection data
Output voltage
with "1" signal
Output current
with "1" signal
Rated value
Permissible range
with "0" signal (residual current)
Output delay (resistive load)
at "1" to "0"
at "1" to "0"
Load resistance range
Lamp load
Wiring two outputs in parallel
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, DC 13
with lamp load
Internal limiting of the inductive shutdown voltage to
Short circuit-proof output
Threshold
Wiring the actuators
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3.32 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0)
24 VDC
13 to 30 V
- 30 V to + 5 V
typ. 7 mA
1.2 ms to 4.8 ms
1.2 ms to 4.8 ms
to IEC 61131, type 1
supported
max. 1.5 mA
with 40-pin front connector
min. L + (- 0.8 V)
0.5 A
5 mA to 0.6 A
max. 0.5 mA
max. 100 μs
max. 500 μs
48 Ω to 4 kΩ
max. 5 W
supported (only outputs of the same group)
not supported
supported
max. 100 Hz
max. 0.5 Hz
max. 10 Hz
typ. L + (- 53 V)
Yes, electronic
typ. 1 A
with 40-pin front connector
Digital modules