Technical data
Transducer selection data
Input voltage
Rated value
•
for "1" signal
•
for "0" signal
•
Input current
with "1" signal
•
Input delay
at "1" to "0"
•
at "1" to "0"
•
Input characteristics
Connection of 2-wire BEROs
Permissible quiescent current
•
Wiring signal transducers
Actuator selection data
Output voltage
with "1" signal
•
Output current
with "1" signal
•
Rated value
Permissible range
with "0" signal (residual current)
•
Output delay (resistive load)
at "1" to "0"
•
at "1" to "0"
•
Load resistance range
Lamp load
Wiring two outputs in parallel
for redundant load control
•
for performance increase
•
Control of a digital input
Switching frequency
with resistive load
•
with inductive load to IEC 947-5-1, DC 13
•
with lamp load
•
Internal limiting of the inductive shutdown voltage to
Short circuit-proof output
Threshold
•
Wiring the actuators
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3.32 Digital IO module SM 323; DI 16/DO 16 x DC 24 V/0.5 A; (6ES7323-1BL00-0AA0)
24 VDC
13 to 30 V
- 30 V to + 5 V
typ. 7 mA
1.2 ms to 4.8 ms
1.2 ms to 4.8 ms
to IEC 61131, type 1
supported
max. 1.5 mA
with 40-pin front connector
min. L + (- 0.8 V)
0.5 A
5 mA to 0.6 A
max. 0.5 mA
max. 100 μs
max. 500 μs
48 Ω to 4 kΩ
max. 5 W
supported (only outputs of the same group)
not supported
supported
max. 100 Hz
max. 0.5 Hz
max. 10 Hz
typ. L + (- 53 V)
Yes, electronic
typ. 1 A
with 40-pin front connector
Digital modules