Parameters Of Analog Output Module Sm 332; Ao 8 X 12 Bit - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Parameter sets of signal modules
A.10 Parameters of analog output module SM 332; AO 8 x 12 Bit
Output types and output ranges
The table below lists all output types/ranges of the analog output modules, including their
codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.)
Table A-29
Output range codes of analog output modules
Output type
disabled
Voltage
Current
See also
Analog modules (Page 6-1)
A.10

Parameters of analog output module SM 332; AO 8 x 12 Bit

A.10
Parameters
The table below shows all parameters you can set at analog output module SM 332; AO 8 x
12 Bit. The comparison shows:
● which parameters you can edit in
● which parameters you can change using SFC 55 "WR_PARM".
Parameters set in
Table A-30
Parameters of SM 332; AO 8 x 12 Bit
Parameters
Diagnostics: Group diagnostics
Diagnostics interrupt enable
Reaction to CPU STOP
Output type
Output range
A-38
Code
Output range
2#0000
disabled
2#0001
1 V to 5 V
0 V to 10 V
± 10 V
2#0010
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
STEP 7
can also be transferred to the module using SFC 56 and SFC 57.
STEP 7
, and
Data record
Programmable, using ...
number
... SFC 55
0
No
1
Yes
Yes
Yes
Yes
Code
2#0000
2#0111
2#1000
2#1001
2#0010
2#0011
2#0100
... PG
Yes
Yes
Yes
Yes
Yes
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04