Siemens SIMATIC S7-300 Manual page 255

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Technical data
Status, interrupts, diagnostics
Interrupts
Hardware interrupt when limit value is exceeded
Hardware interrupt at end of cycle
Diagnostic interrupt
Diagnostics functions
Group error display
Reading diagnostics information
Transducer selection data
Input range (rated values) / input impedance
Voltage
Current
Permissible voltage at voltage input (destruction limit)
Permissible current at current input (destruction limit)
Wiring signal transducers
for voltage measurement
for current measurement
as 2-wire transducer
as 4-wire transducer
Interference frequency for 4-channel mode is "All"
1)
Interference frequencies 50/60/400 Hz are designated as "All"
2)
Series-mode rejection for 8-channel mode is reduced as follows:
3)
50 Hz > 70 db
60 Hz > 70 db
400 Hz > 80 dB
50/60/400 Hz > 90 dB
In 4-channel mode, the converted value tunes to 100% within 80 ms. The value
4)
established in this process is set every max. 10 ms.
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0)
Programmable channels 0 - 7
programmable
programmable
programmable
red LED (SF)
supported
± 5 V / 2 MΩ
1 V to 5 V / 2 MΩ
± 10 V / 2 MΩ
0 mA to 20 mA / 250 Ω
4 mA to 20 mA / 250 Ω
± 20 mA / 250 Ω
35 V continuous; 75 V for max. duration of 1 s (duty
factor 1:20)
40 mA
with 40-pin front connector
supported
possible, with separate transducer supply
supported
Analog modules
6-21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents