Technical data
Status, interrupts, diagnostics
Interrupts
Hardware interrupt when limit value is exceeded
•
Hardware interrupt at end of cycle
•
Diagnostic interrupt
•
Diagnostics functions
Group error display
•
Reading diagnostics information
•
Transducer selection data
Input range (rated values) / input impedance
Voltage
•
Current
•
Permissible voltage at voltage input (destruction limit)
Permissible current at current input (destruction limit)
Wiring signal transducers
for voltage measurement
•
for current measurement
•
as 2-wire transducer
as 4-wire transducer
Interference frequency for 4-channel mode is "All"
1)
Interference frequencies 50/60/400 Hz are designated as "All"
2)
Series-mode rejection for 8-channel mode is reduced as follows:
3)
50 Hz > 70 db
60 Hz > 70 db
400 Hz > 80 dB
50/60/400 Hz > 90 dB
In 4-channel mode, the converted value tunes to 100% within 80 ms. The value
4)
established in this process is set every max. 10 ms.
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0)
Programmable channels 0 - 7
programmable
programmable
programmable
red LED (SF)
supported
± 5 V / 2 MΩ
1 V to 5 V / 2 MΩ
± 10 V / 2 MΩ
0 mA to 20 mA / 250 Ω
4 mA to 20 mA / 250 Ω
± 20 mA / 250 Ω
35 V continuous; 75 V for max. duration of 1 s (duty
factor 1:20)
40 mA
with 40-pin front connector
supported
possible, with separate transducer supply
supported
Analog modules
6-21