Analog modules
6.12 Analog output module SM 332; AO 4 x 16 bit; isochronous; (6ES7332-7ND02-0AB0)
Technical data
Voltage output
Short-circuit protection
•
Short-circuit current
•
Current output
Noload voltage
•
Destruction limit against external voltages/currents
Voltage at outputs to M
•
Current
•
Wiring the actuators
For voltage output
•
–
4-wire connection (measuring lead)
For current output
•
–
2-wire connection
6.12.1
Output ranges SM 332; AO 4 x 16 Bit
Introduction
You can configure the outputs for operation as voltage or current outputs, or disable these.
You configure the output circuits at the "output type" parameter in
The output type "Voltage" and output range "± 10 V" are set by default at the module. You
can always use this combination of output type and range without having to program the SM
332; AO 4 x 16 Bit in
Output ranges
You program the output ranges for voltage and current outputs in
Table 6-34
Selected type of output
Voltage
Current
6-112
ANA
STEP 7
Output ranges SM 332; AO 4 x 16 Bit
Yes
max. 40 mA
max. 18 V
max. 15 V, continuous
75 V for the duration of max. 1 s
(duty factor 1:20) 20)
max. 50 mA d.c.
with 20-pin front connector
supported
supported
.
Output range
1 V to 5 V
0 V to 10 V
± 10 V
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
STEP 7
.
STEP 7
.
S7-300 Automation System Module data