Relay Output Module Sm 322; Do 16 X Rel. Ac 120/230 V; (6Es7322-1Hh01-0Aa0) - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Diagnostic interrupt
When diagnostic interrupts are enabled, incoming error events (initial occurrence) and
outgoing error events (error is cleared) are reported by means of interrupt.
The CPU interrupts execution of the user program and processes diagnostic interrupt OB 82.
You can call SFC 51 or 59 in OB82 in the user program to view detailed diagnostic data
output by the module.
Diagnostics data remain consistent until the program exits OB 82. The module
acknowledges the diagnostic interrupt when the program exits OB82.
Load restrictions in horizontal mounting position
In horizontal mounting position, the module loads must be restricted so that two adjacent
inputs or outputs do not exceed their rated load.
Load restrictions in vertical mounting position
In vertical mounting position, the module loads must be restricted so that four adjacent inputs
or outputs do not exceed their rated load.
See also
Parameters of SM 322; DO 8 x DC 24 V/0.5 A (Page 3-77)
3.28
Relay output module SM 322; DO 16 x Rel. AC 120/230 V;
3.28
(6ES7322-1HH01-0AA0)
Order number
6ES7322-1HH01-0AA0
Properties
Properties of SM 322; DO 16 x Rel. AC 120/230 V:
● 16 outputs, electrically isolated in groups of 8
● Rated load voltage 24 VDC to 120 VDC, 48 VAC to 230 VAC
● Suitable for AC/DC solenoid valves, contactors, motor starters, FHP motors and signal
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04

3.28 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0)

lamps.
Digital modules
3-93