Analog modules
6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0)
Technical data
Isolation test voltage
Current consumption
from the backplane bus
from power supply L+
Power loss of the module
Formation of analog values
Measuring principle
Mode of operation
Integration/conversion time/resolution (per channel)
programmable
Basic conversion time in ms
Additional conversion time for resistance measurement in ms
Additional conversion time for wire-break monitoring in ms
Resolution (including overshoot range)
Noise suppression at interference frequency f1 in Hz
Measured value smoothing
Conversion time (per channel)
Basic execution time of the module (all channels enabled)
Mode of operation
Integration/conversion time/resolution (per channel)
programmable
Basic conversion time in ms
Additional conversion time for resistance measurement in ms
Additional conversion time for wire-break monitoring in ms
Resolution (including overshoot range)
Noise suppression at interference frequency f1 in Hz
Measured value smoothing
Conversion time (per channel)
Basic execution time of the module (all channels enabled)
Mode of operation
Integration/conversion time/resolution (per channel)
programmable
Basic conversion time in ms
Additional conversion time for resistance measurement in ms
Additional conversion time for wire-break monitoring in ms
Resolution (including overshoot range)
Noise suppression at interference frequency f1 in Hz
Measured value smoothing
Basic execution time of the module (all channels enabled)
6-76
500 VDC
max. 100 mA
max. 240 mA
typ. 4.6 W
Integrating
8-channel mode (hardware filter)
Yes
80
100*
0
16 bits (including sign)
400 / 60 / 50
None / low/ average/ high
100 ms
200 ms
8-channel mode (software filter)
Yes
8 / 25 / 30
25/ 43/ 48*
0
16 bits (including sign)
400 / 60 / 50
None / low/ average/ high
25 ms/ 43 ms/ 48 ms
50 ms/ 86 ms/ 96 ms
4-channel mode (hardware filter)
Yes
3,3****
100*
100**
16 bits (including sign)
400 / 60 / 50
None / low/ average/ high
10 ms
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04