3.24 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0)
3.24.4

Interrupts of SM 322; DO 8 x DC 24 V/0.5 A

Introduction
The SM 322; DO 8 x DC 24 V/0.5 A can trigger diagnostic interrupts.
For detailed information on the OBs and SFCs mentioned below, refer to the
Help.
Enabling interrupts
There is no default interrupt setting, i.e. interrupts are disabled if parameters are not set
accordingly. Program the interrupt enable parameter in STEP 7.
Diagnostic interrupt
When diagnostic interrupts are enabled, incoming error events (initial occurrence) and
outgoing error events (error is cleared) are reported by means of an interrupt.
The CPU interrupts user program execution, and executes diagnostic interrupt OB82.
You can call SFC 51 or 59 in OB82 in the user program to view detailed diagnostic data
output by the module.
Diagnostics data remain consistent until the program exits OB 82. The module
acknowledges the diagnostic interrupt when the program exits OB82.
See also
Parameters of SM 322; DO 8 x DC 24 V/0.5 A (Page 3-77)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
Digital modules
STEP 7
Online
3-81