Table 5-25 Representation Of The Analog Values Of Thermocouples Type J - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
Representation of the analog values of thermocouples type J
Table 5-25
Representation of the analog values of thermocouples type J
Type J in
Units
°C
dec
> 1450.0
32767
1450.0
14500
:
:
1201.0
12010
1200.0
12000
:
:
-210.0
-2100
< -210.0
< -2100
Faulty wiring (polarity reversal, or open inputs, for example), or transducer error in the negative range
(wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting
at ...
... F31C
, and to output 8000
H
Representation of the analog values of thermocouples type K
Table 5-26
Representation of the analog values of thermocouples type K
Type K in
Units
°C
dec
> 1622.0
32767
1622.0
16220
:
:
1373.0
13730
1372.0
13720
:
:
-270.0
-2700
< -270.0
< -2700
Faulty wiring (polarity reversal, or open inputs, for example), or transducer error in the negative range
(wrong type of thermocouple, for example) will cause the analog input module to signal underflow, starting
at ...
... F0C4
, and to output 8000
H
5-14
Type J in °F
hexa-
decimal
7FFF
> 2642.0
H
38A4
2642.0
H
:
:
2EEA
2193.8
H
2EE0
2192.0
H
:
:
F7CC
-346.0
H
<F7CC
< -346.0
H
.
... EA0C
, and to output 8000
H
H
Type K in
°F
hexa-
decimal
7FFF
> 2951.6
H
3F5C
2951.6
H
:
:
35A2
2503.4
H
3598
2501.6
H
:
:
F574
-454.0
H
< F574
< -454.0
H
.
... E5D4
, and to output 8000
H
H
Units
Type J in K
dec
hexa-
decimal
32767
7FFF
> 1723.2
H
26420
6734
1723.2
H
:
:
:
21938
55B2
1474.2
H
21920
55A0
1473.2
H
:
:
:
-3460
F27C
63.2
H
< -3460
<F27C
< 63.2
H
.
... FDC8
H
Units
Type K in K
dec
hexa-
decimal
32767
7FFF
> 1895.2
H
29516
734C
1895.2
H
:
:
:
25034
61CA
1646.2
H
25061
61B8
1645.2
H
:
:
:
-4540
EE44
0
H
< -4540
<EE44
< 0
H
.
... FB70
H
Units
dec
hexa-
decimal
32767
7FFF
H
17232
4350
H
:
:
14742
3996
H
14732
398C
H
:
:
632
0278
H
< 632
< 0278
H
, and to output 8000
.
H
H
Units
dec
hexa-
decimal
32767
7FFF
H
18952
4A08
H
:
:
16462
404E
H
16452
4044
H
:
:
0
0000
H
< 0
< 0000
H
, and to output 8000
.
H
H
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
Range
Overflow
Overshoot
range
Nominal range
Underflow
Range
Overflow
Overshoot
range
Nominal
range
Underflow