Technical data
Operational limit (across temperature range, relative to input range)
Voltage input
Current input
Resistance
Thermocouple
Resistance thermometers
Basic error limit (operational error limit at 25 °C, relative to input range)
Voltage input
Current input
Resistance
Thermocouple
Resistance thermometers
Temperature error (relative to input range)
Linearity error (relative to input range)
Repetition accuracy (in transient state at 25 °C, relative to
input range)
Temperature error of internal compensation
Status, interrupts, diagnostics
Interrupts
Hardware interrupt when limit has been exceeded
Diagnostic interrupt
Diagnostics functions
Group error display
Reading diagnostics information
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.7 Analog input module SM 331; AI 8 x 12 Bit;(6ES7331-7KF02-0AB0)
80 mV
250 mV to 1000 mV
2.5 V to 10 V
3.2 mA to 20 mA
150 Ω; 300 Ω; 600 Ω
Types E, N, J, K, L
Pt 100/Ni 100
Pt 100 Klima
80 mV
250 mV to 1000 mV
2.5 V to 10 V
3.2 mA to 20 mA
150 Ω; 300 Ω; 600 Ω
Types E, N, J, K, L
Pt 100/Ni 100
Pt 100 Klima
± 0.005 %/K
± 0,05 %
± 0,05 %
± 1 %
programmable
Channels 0 and 2
programmable
programmable
red LED (SF)
supported
Analog modules
± 1 %
± 0,6 %
± 0,8 %
± 0,7 %
± 0, 7 %
± 1, 1 %
± 0, 7 %
± 0, 8 %
± 0,7 %
± 0,4 %
± 0,6 %
± 0,5 %
± 0,5 %
± 0,7 %
± 0,5 %
± 0,6 %
6-55