6.11.1
Output ranges SM 332; AO 8 x 12 Bit
Introduction
You can configure the outputs for operation as voltage or current outputs, or disable them.
You configure the outputs at the "output type" parameter in
The output type "Voltage" and output range "± 10 V" are set by default at the module. You
can always use this combination of output type and range without having to program the
SM 332; AO 8 x 12 Bit in
Table 6-32
Selected type of output
Voltage
Current
See also
Representation of the analog values of analog output channels (Page 5-18)
6.11.2
Adjustable parameters
Introduction
For general information on programming analog modules, refer to the chapter
analog modules
The table below provides an overview of configurable parameters, including defaults:
Table 6-33
Summary of parameters SM 332; AO 8 x 12 Bit
Parameters
Enable
Diagnostic interrupt
•
Diagnostics
Group diagnostics
•
Output
Output type
•
Output range
•
Reaction to CPU STOP ASS
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6.11 Analog output module SM 332; AO 8 x 12 Bit; (6ES7332-5HF00-0AB0)
STEP 7
Output ranges
.
Range of values
Yes/no
Yes/no
disabled
Voltage
Current
output ranges
See table of
Outputs zero
current/voltage
Hold last value
HLV
Set substitution
SSV
value
.
Output range
1 V to 5 V
0 V to 10 V
± 10 V
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
Default
No
No
V
± 10 V
ASS
Analog modules
STEP 7
.
Programming
Parameter
Scope
type
Dynamic
Module
static
Channel
Dynamic
Channel
Dynamic
Channel
6-105