Commissioning
Figure 4.1
1
Battery
2
Battery cable plugged into battery connector
As soon as the battery is connected, the adapter initializes.
- The occupation of the terminals is checked.
- The type of device connected is checked.
- If a HART device is connected, its data are read into the adapter.
- The LEDs indicate the status of the device. See chapter 6.1.1
- The adapter is now ready for commissioning.
4.3

Initial Configuration via HART Modem

For security reasons, the Network ID and Join Key must be configured through a wired
connection before the device can connect itself to a WirelessHART network. To do so, you can
use an Ex ia certified HART modem that connects to a PC/Laptop using the USB interface or
the RS232 interface.
Caution!
Loss of intrinsic safety
If Ex i protected circuits have been operated with non-intrinsically safe circuits, they must no
longer be used as Ex i protected circuits.
To maintain the Ex i rating of the WirelessHART adapter, use an Ex i rated HART modem to
communicate with the WirelessHART adapter.
Connecting the device to a PC/Laptop via HART modem
Install the HART modem drivers on your PC/Laptop according to the instructions given by the
manufacturer.
1. If necessary, open the housing cover by unscrewing the four captive Phillips screws.
Figure 3.16 on page 26