Pepperl+Fuchs WHA-ADP2-F8B2 Z1 Series Manual page 51

Wirelesshart adapter
Table of Contents

Advertisement

WHA-ADP2-F8B2-*-**-Z1(-EX1)
Configuration
Burst Mode 1 ... 10 Parameters
Parameter
Burst Mode
Control Code
Device Index
Period
Max. Period
Trigger Mode
Device Variable
Class (Trigger)
Unit Code
(Trigger)
Trigger Level
Description
Switches burst mode on or off ("Wireless" = on).
The following parameters in this table can only be edited if
Burst Mode Control Code is set to "Wireless". Otherwise
they are grayed out.
The field will also show "Off" if the parameters are downloaded
when the adapter is not in the network. The parameters are
retained and become active when the adapter joins the
network.
Selects the device via its long tag for which the burst mode
applies.
<Adapter Long Tag>: Adapter parameters are transmitted.
<Device Long Tag>: Device parameters are transmitted.
For HART devices of Revision 5 or lower, the "Message"
serves as the long tag. See chapter 4.1
When the trigger mode is set to "continuous", determines
the period in hh:mm:ss that elapses between burst
messages.
When the trigger mode is not set to "continuous",
determines the scan rate in hh:mm:ss for checking
whether the trigger condition for a burst message is
fulfilled.
The minimum setting is 8 seconds.
When the Trigger Mode is not set to "continuous", determines
the maximum period in hh:mm:ss that may elapse between
two burst messages when the conditions for the trigger are not
fulfilled.
Determines the event that triggers a burst message from the
device.
Continuous: A burst message is published continuously at
intervals determined by Period.
Window: a burst message is triggered when the source
value deviates more than the specified trigger value.
Rising: a burst message is triggered when the source
value rises above the specified trigger value.
Falling: a burst message is triggered when the source
value falls below the specified trigger value.
On-Change: a burst message is triggered when any value
in the message changes.
If the conditions are not met for Trigger Modes "Window",
"Rising", "Falling" and "On-Change", a burst message is sent
at intervals determined by Max. Period.
Determines the device variable that is used to trigger the burst
message, e.g. Temperature.
Engineering unit used by the trigger variable, e.g. °C
Value of the source variable which is used to trigger the burst
message, e.g. 150°C
Default
Off
Not
selected
00:30:00
01:00:00
Continuous
Not
classified
Not used
0
51