WHA-ADP2-F8B2-*-**-Z1(-EX1)

Commissioning

4
Commissioning
Warning!
Do not operate the power switch in a hazardous location.
4.1

Connected HART Device(s)

It is recommended that the connected HART device is commissioned before the adapter.
Note!
It is not necessary to assign different HART addresses for different adapters. The
addresses used on the network also incorporate the serial number of the adapters and
are automatically unique for each adapter.
4 ... 20 mA devices require no pre-configuration. The scaling and any linearization are
configured within the adapter DTM.
Parameterizing the field device
1. Connect a configuration tool, for example, PACTware
modem.
If the adapter shall power the field device, first power the adapter by connecting the battery
and then continue with this step. During the start-up phase of the adapter, the field device
goes on and off again. If the field device does not power up again after the communication
started, power the field device for 5 minutes (time can be configured in adapter DTM) by
pushing the adapter button for more than 10 seconds until the red LED flashes.
2. Set the following parameters for the field device:
HART address: sets the output mode of the device (0 = 4 ... 20 mA; 1 ... 15 = HART)
• If the device is connected to an existing 4...20 mA loop, use the address = 0
• Otherwise use address = 1 for HART multidrop mode with a 4 mA current output.
• If more than one HART device is connected (up to 4 are allowed if externally
Device Tag: identifies the measuring point.
Long Tag: identifies the device on the wireless network.
Long Tags are available from HART Version 6.0 onwards. For earlier versions, for
example, HART 5 instruments, use the Message instead.
4.2

Connecting the Battery

Danger!
Batteries in hazardous areas
Batteries from Pepperl+Fuchs for this device may be brought into hazardous areas. However,
always check if the battery is intact before transporting it into hazardous areas. Always
transport batteries enclosed inside their original packages or already installed inside the
device.
Danger!
Loss of intrinsic safety
The use of batteries other than specified voids the qualification for use in hazardous areas.
Only use batteries of type W-BAT-B2-Li from Pepperl+Fuchs.