WHA-ADP2-F8B2-*-**-Z1(-EX1)
Troubleshooting
Fault
The parameters
of an
independently
operating 4-wire
field device
cannot be read
by the adapter
DTM.
Wired
Communication
Dialog: see
chapter 5.5
The parameters
of a field device in
a control loop
cannot be read
by the adapter
DTM
Wired
Communication
Dialog: see
chapter 5.5
PACTware
cannot find a field
device connected
to Terminals 1 + 2
or 2 + 3 of the
adapter when
communicating
through a HART
modem
connected to
Terminals 5/7 and
6/8
Adapter does not
restart after
disconnecting
and connecting
the battery
PACTware
cannot find a
connected HART
device when
communicating
via
WirelessHART
Gateway.
78
Possible Cause(s)
Device does not support HART
protocol
Device address not found by the
Adapter DTM
Device not powered
Device not wired up correctly
Device does not support HART
protocol
Device address not found by the
Adapter DTM
Device not powered
Device not wired up correctly
PLC or Remote I/O acting as primary
master forces adapter to operate as
slave
TM
For control loops with
communication resistor:
Device address not found by the
HART communication DTM
For control loops without
communication resistor, for 2-wire
devices powered by adapter and for
4 wire devices:
No communication path to device
(design feature)
For all connections:
Device not powered
Battery reconnected before adapter
power fully discharged
TM
Device does not support HART
protocol
Device address not found by the
Adapter DTM
Device not powered
Device powered, but shuts down
before it communicates
Corrective Action(s)
Parameters can be read from a
HART device only.
Check the highest scan address.
See chapter 5.5
Check the power supply of the
device.
Check the wiring.
Parameters can be read from a
HART device only.
Check the highest scan address.
See chapter 5.5
Check loop power.
Check the wiring of the device.
Configure adapter as secondary
master. See chapter 5.5
Configure the correct address range.
See chapter 4.5.2
Depending upon circuit, connect
modem across terminals 1 and 2
or 2 and 3.
Configure the correct address
range. See chapter 4.5.2
Check the power supply of the
device.
1. Disconnect the battery again.
2. Press button for 3 seconds.
3. Wait one minute.
4. Reconnect the battery.
Parameters can be read from a
HART device only.
Check the highest scan address.
See chapter 5.5
See second fault.
Increase power supply parameter
"Lead Time" in steps of 10 s until the
fault is eliminated. See chapter 5.8