Application Settings

5.7.1
4 ... 20 mA
When a HART device is connected to the adapter, all parameters are read via the digital signal.
It is possible, however, to connect a 4 ... 20 mA device to the adapter. In this case the
4 ... 20 mA signal can be scaled as desired in the DTM and a linearization can be made if
necessary. In addition, current values can be set which correspond to the limits of the
proportional range and the fault signal of the device. Should these current limits be violated, an
appropriate warning or alarm signal is transmitted by the adapter.
Description
Variable to be output as primary variable (PV)
Engineering units of the primary variable
Variable to be output as secondary variable (SV)
Engineering units of the secondary variable (fixed)
Variable to be output as tertiary variable (SV)
Engineering units of the tertiary variable (fixed)
Variable to be output as quaternary variable (SV)
Engineering units of the quaternary variable (fixed)
Default
Loop Current
(fixed)
mA (fixed)
Temperature
°C
Battery Voltage
V
Normalized
Consumer Energy
Ah